Insulation calculator
Choose the attic, the walls or a floor, enter its size and pick your climate zone. The calculator gives the R-value the energy code asks for, and the bags of batts or rolls, or the bags of blown-in insulation and the depth to blow, to reach it.
How the calculator works
- Area. Attic or floor: length × width. Walls: length of all walls × wall height, less 20 sq ft (1.86 m²) for each door and 15 sq ft (1.39 m²) for each window.
- Target. The R-value your climate zone asks for, from the 2021 International Energy Conservation Code, Table R402.1.3. ENERGY STAR gives the same values for attics and floors.
- R-value to add. In an attic, the target less the R-value already there.
- Blown-in. The calculator takes the row of the bag's chart that is equal to the R-value to add, or else the next higher row. The bags are the area divided by the area one bag covers in that row, rounded up. The row also gives the least depth to blow.
- Batts between the framing. A batt fills the space between two studs or joists, so the framing takes the rest of the width. A 15 in batt between studs 16 in on center covers 15/16 of the wall. The batt area is the area × batt width ÷ spacing, and the bags are the batt area divided by what one bag holds, rounded up.
- Batts in an attic. As many layers as the R-value to add needs. On a bare attic floor the bottom layer goes between the joists and the layers above it go across them. Over old insulation every layer covers the whole floor.
- Batt choice. Unless you pick one, the calculator takes the thinnest batt that reaches the target: for walls R-13, R-15, R-19 or R-21; for floors R-19, R-30 or R-38. In an attic it takes the batt that needs the fewest layers, R-30 or R-38.
Worked example
An attic over a ceiling of 30 × 40 ft (9.1 × 12.2 m) in climate zone 4 has 3½ in of old R-11 batts. The owner blows in AttiCat fiberglass.
| Step | Calculation | Result |
|---|---|---|
| Area | 30 ft × 40 ft | 1,200 sq ft (111.5 m²) |
| Target for zone 4 | Table R402.1.3 | R-60 (RSI 10.57) |
| To add | R-60 − R-11 | R-49 (RSI 8.63) |
| Chart row | AttiCat, R-49 | 25 bags for 1,000 sq ft, at least 17 in (43 cm) |
| One bag covers | 1,000 sq ft ÷ 25 | 40 sq ft (3.7 m²) |
| Bags | 1,200 sq ft ÷ 40 sq ft | 30 bags |
With Greenfiber cellulose the R-49 row asks for 72.6 bags for 1,000 sq ft at 14.3 in (36 cm): 88 bags. With batts, two layers of R-30 give R-71 for 45 bags of 10 pieces, 16 × 48 in.
For walls: 140 ft of wall 8 ft high in zone 2, with 2 doors and 8 windows, is 1,120 − 40 − 120 = 960 sq ft. R-13 batts 15 in wide between studs 16 in on center cover 960 × 15/16 = 900 sq ft. A bag of 13 batts, 15 × 93 in, holds 125.9 sq ft, so the walls take 8 bags.
R-value by climate zone
The least R-values of the 2021 International Energy Conservation Code, Table R402.1.3. ENERGY STAR recommends the same values when you add insulation to an attic or a floor. "+ 5ci" means R-5 of continuous insulation, such as rigid foam boards, over the sheathing.
| Zone | Attic | Attic with 3–4 in already, add | Wood-frame wall | Floor |
|---|---|---|---|---|
| 1 | R-30 | R-25 | R-13, or R-10ci | R-13 |
| 2 | R-49 | R-38 | R-13, or R-10ci | R-13 |
| 3 | R-49 | R-38 | R-20, R-13 + 5ci, or R-15ci | R-19 |
| 4A, 4B | R-60 | R-49 | R-30, R-20 + 5ci, R-13 + 10ci, or R-20ci | R-19 |
| 4C, 5 | R-60 | R-49 | R-30, R-20 + 5ci, R-13 + 10ci, or R-20ci | R-30 |
| 6 | R-60 | R-49 | R-30, R-20 + 5ci, R-13 + 10ci, or R-20ci | R-30 |
| 7, 8 | R-60 | R-49 | R-30, R-20 + 5ci, R-13 + 10ci, or R-20ci | R-38 |
For walls the calculator aims at the cavity: R-13 in zones 1 and 2, R-20 in zone 3, and R-20 with R-5 over the sheathing in zones 4 to 8. In metric, multiply an R-value by 0.1761 for RSI in m²·K/W. Your state or city can adopt another edition of the code, or change it.
Batts and rolls
The calculator uses the sizes of Owens Corning EcoTouch batts. Packages differ by store and maker; the bag states the area it holds, so enter that under "Other package size".
| Batt | Thickness | 16 in on center | 24 in on center |
|---|---|---|---|
| R-13 | 3½ in (89 mm) | 15 × 93 in, 13 a bag, 125.9 sq ft | 23 × 93 in, 11 a bag, 163.4 sq ft |
| R-15 | 3½ in (89 mm) | 15 × 93 in, 8 a bag, 77.5 sq ft | 23 × 93 in, 7 a bag, 104.0 sq ft |
| R-19 | 6¼ in (159 mm) | 15 × 93 in, 8 a bag, 77.5 sq ft | 23 × 93 in, 8 a bag, 118.8 sq ft |
| R-21 | 5½ in (140 mm) | 15 × 93 in, 8 a bag, 77.5 sq ft | 23 × 93 in, 6 a bag, 89.1 sq ft |
| R-30 | 9½ in (241 mm) | 16 × 48 in, 10 a bag, 53.3 sq ft | 24 × 48 in, 10 a bag, 80.0 sq ft |
| R-38 | 12 in (305 mm) | 16 × 48 in, 8 a bag, 42.7 sq ft | 24 × 48 in, 8 a bag, 64.0 sq ft |
| R-19 roll | 6¼ in (159 mm) | 15 in × 39 ft 2 in, 49.0 sq ft | 23 in × 39 ft 2 in, 75.1 sq ft |
| R-30 roll | 9½ in (241 mm) | 15 in × 25 ft, 31.3 sq ft | 23 in × 25 ft, 47.9 sq ft |
The area on a bag of batts is the batts themselves: 13 pieces of 15 × 93 in make 125.9 sq ft. That is why the calculator takes the framing out of the wall area before it divides.
Blown-in insulation
Every bag of loose fill carries a chart with the bags for 1,000 sq ft and the least depth for each R-value. The calculator uses these two charts.
| R-value | AttiCat fiberglass: bags for 1,000 sq ft | Depth | Greenfiber cellulose: bags for 1,000 sq ft | Depth |
|---|---|---|---|---|
| R-13 | 5.9 | 5 in | 15.2 | 3.9 in |
| R-19 | 9 | 7 in | 22.6 | 5.7 in |
| R-30 | 14.6 | 10¾ in | 38.6 | 8.9 in |
| R-38 | 19 | 13½ in | 52.6 | 11.2 in |
| R-49 | 25 | 17 in | 72.6 | 14.3 in |
| R-60 | 31.5 | 20½ in | 92.5 | 17.3 in |
The charts also have rows for R-11, R-22, R-26, R-32, R-40, R-44, R-48 and R-50. Cellulose settles: Greenfiber's depth is the depth when installed, and the chart's R-value holds at the settled depth, a little less. Owens Corning states that you get the R-value only with both the bags and the depth on the chart.
How much is already there
Measure the depth of the old insulation in a few places and compare it with these products. Old insulation that is packed down, wet or patchy gives less.
| Old insulation | Depth | About |
|---|---|---|
| Fiberglass batts | 3½ in (9 cm) | R-11 to R-15 |
| Fiberglass batts | 6 in (15 cm) | R-19 |
| Fiberglass batts | 9½ in (24 cm) | R-30 |
| Blown fiberglass | 5 in (13 cm) | R-13 |
| Blown fiberglass | 10¾ in (27 cm) | R-30 |
| Cellulose | 3.6 in (9 cm) settled | R-13 |
| Cellulose | 8.3 in (21 cm) settled | R-30 |
Questions
How much insulation do I need in my attic?
R-30 in climate zone 1, R-49 in zones 2 and 3, and R-60 in zones 4 to 8. With blown-in fiberglass that is about 10¾, 17 and 20½ in. Subtract what is already there: an attic with R-11 in zone 4 needs R-49 more.
How many bags of blown-in insulation do I need for 1,000 sq ft?
With AttiCat fiberglass: 15 bags for R-30, 19 for R-38, 25 for R-49 and 32 for R-60. With Greenfiber cellulose: 39, 53, 73 and 93 bags. The chart on your bag decides.
How many bags of R-13 insulation do I need for 1,000 sq ft of wall?
Eight bags of 13 batts, 15 × 93 in. The studs 16 in on center take 1/16 of the wall, so the batts cover 937.5 sq ft, and one bag holds 125.9 sq ft.
What R-value do I need for walls?
R-13 in zones 1 and 2. In zone 3, R-20 in a 2 × 6 wall, or R-13 with R-5 of rigid insulation over the sheathing. In zones 4 to 8, R-20 with R-5 over the sheathing, R-13 with R-10, or R-30 in a deeper wall.
What R-value do I need under a floor?
R-13 in zones 1 and 2, R-19 in zones 3 and 4, R-30 in zones 4C, 5 and 6, and R-38 in zones 7 and 8, for a floor over a crawl space, a garage or the open air.
What is the R-value of 6 inches of insulation?
About R-19 for fiberglass batts: an R-19 batt is 6¼ in thick. Blown fiberglass gives less for its depth, R-19 at 7 in; cellulose gives more, R-19 at 5.7 in.
Do I take the studs out of the wall area?
Yes, for batts. The area on a bag is the area of the batts, and the batts go only between the studs. The calculator takes out the part of each bay the batt does not fill.
Can I put new insulation over old insulation?
Yes, in an attic. The R-values add up, so enter the R-value already there and the calculator counts only what is missing. Greenfiber's guide shows it: 6 in of old batts, R-19, need R-19 more to reach R-38.
Sources
- ENERGY STAR: Recommended home insulation R-values, after the 2021 IECC Table R402.1.3
- NAHB: Suggested amendments to the 2021 IECC, with Table R402.1.3 as published (PDF)
- University of Illinois Smart Energy Design Assistance Center: 2021 IECC changes, wall R-values for zones 4 and 5 (PDF)
- U.S. Department of Energy: Consumer guide to home insulation, with the climate zone map (PDF)
- Owens Corning: EcoTouch PINK Fiberglas insulation, fact sheet with batt sizes and packages (PDF)
- Owens Corning: AttiCat blown-in insulation, fact sheet with the coverage chart (PDF)
- Greenfiber: Do-it-yourself attic installation, with the Sanctuary coverage chart (PDF)
- NIST Special Publication 811, Appendix B.9: conversion of R-value to m²·K/W
Checked on 15 November 2026. Packages and charts differ by product; read the bag you buy. Your local building department decides the rules for your house.